These time switches provide a different “ON/OFF”
program each day of the week. They also provide for 4 pole single throw and 4
pole (2NO/2NC) switching. This series provides true 7-day load control with
minimum ON and minimum OFF times of 3-1/2 hours. The “BC” models with carryover
provide a carryover of 16 hours minimum to maintain accurate load control even
during power failure. When power resumes, the carryover automatically rewinds
itself. Only 1 hour is required to rewind the carryover for each 2 hours of
outage.
Specifications:
- Model: T7801B
- Model Number Steel NEMA3R Case:-
- Model with CarryOver: T7801BC
- Switch: 2NO/2NC
- Clock Motor Volts 60Hz: 125
- Amps (per pole): 40
- Case: Steel in gray finish 12-1/2" (31.7
cm) high, 8-1/4" (21.0 cm) wide, 4" (10.2 cm) deep. Indoor type with toggle
action drawbolt and locking feature. Four mounting holes on back. Separate
grounding terminal.
- Knockouts: Combination 1/2"-3/4" nominal
knockouts, two on back, one on each side and two on bottom. Also one 1" nominal
on bottom center.
- Optional Enclosures: See Time Switch
Cases for optional enclosures
- Special Voltages and Cycles: See Time
Switch Motors for available motors. Contact factory for availability of time
switch with 50 cycle or other voltages.
- Switch Rating: Each Pole 40 amp
resistive, 120-480 VAC; 40 amp tungsten, inductive or 1000 VA pilot duty,
120-277 VAC; 2 HP (24 FLA) 120 VAC; 5 HP (28 FLA) 240 VAC single phase; 7-1/2 HP
(28 FLA) 208 VAC three phase; 10 HP (28 FLA) 240 VAC three phase.
- Carryover: Minimum time - mechanical
operation: 16 hours. Carryover accuracy +/-2%.
Note: All models (B or BC suffix) have
separate clock motor terminals for switching circuits not on line voltage.
Applications:
- Heating
- Outdoor Lighting
- Ventilating Systems
- Air Conditioning
- Motors
- Fans
- Pumps
- Signs
- Filters
- Indoor Lighting
- Billboards
- 3 Phase Loads